RCT 6000VA / 4800W Online Rackmount UPS
R19,799.00
Shop Online
and fill your cart
Choose Payflex at checkout
Get approved and
pay 25% today
with your debit
or credit card
Pay the remainder
over 6-weeks.
No interest.
No fees.
- Capacity: 6000 VA / 4800 W
- Frequency Range: 46~54 Hz or 56~64 Hz
- Battery Type: 12 V / 9 Ah
- Pure Sinewave
- Power Input Cable Not Included – RCT INPUT POWER CORD 3pin SA Plug to IEC C19
- Description
- WARRANTY
- Reviews (0)
Description
This UPS can charge up to 90% in battery capacity within a 9-hour period. This UPS has a built-in Microprocessor control that guarantees high reliability. It also includes free monitoring software as well as Overload, discharge, and overcharge protection.
Capacity
6000 VA / 4800 W
Input
Voltage
208/220/230/240 VAC
Voltage Range
110-300 VAC @ 50% load, 176-300 VAC 100% load
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
≥ 0.99 @ nominal voltage (100% load)
Output
Output Voltage
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
±1%
Frequency Range (Synchronized Range)
46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≤ 3 % THD (Linear Load) ; ≤ 5 % THD (Non-linear Load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
92 %
Battery Mode
90 %
Battery
Standard Model
Battery Type
12 V / 9 Ah
Numbers
16
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current (max.)
1 A / 2 A
Charging Voltage
218.4 VDC ± 1%
Long-run Model
Battery Type
Depending on the applications running
Numbers
16~20 (Adjustable)
Charging Current (max.)
1A/2A/4A/6A (Adjustable, 6 A is only available for 16pcs batteries)
Charging Voltage
218.4 VDC ± 1% (Based on 16pcs batteries)
Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding every twice second
Fault
Continuously Sounding
Physical
Standard Model
Dimensions, D X W X H(mm)
UPS Unit: 500x438x88 [2U]
Battery Pack: 668x438x88 [2U]
Net Weight (kgs)
UPS Unit: 15
Battery Pack: 48
Long-run Model
Dimensions, D X W X H(mm)
500 x 438 x 88[2U]
Net Weight (kgs)
15
Environment
Humidity
0-95 % RH @ 0- 40° (non-condensing)
Noise Level
Less than 55dB @ 1 meter
Management
Smart RS-232 and USB
Supports Windows® 2000/2003/XP/Vista/2008. Windows® 7/8, Linus, and MAC
Optional SNMP
Power management from SNMP manager and web browser
1 Year
Be the first to review “RCT 6000VA / 4800W Online Rackmount UPS”
You must be logged in to post a review.
Reviews